LQ -40℃~-110℃
Air Cooling Chiller
· Air Flow 15m³/h~100m³/h
· Heat Axchange Area 0.8㎡~13㎡
· Power 1.2kW~11.5kW
- Gas Refrigeration Unit
- Gas heat exchange system withstand pressure 20bar
- All use environmentally friendly refrigerants
- Using secondary subcooling technology, rapid cooling and low limit temperature
- Using Siemens S7 PLC, 7-inch touch screen, automatic control operation, and with temperature curve display, temperature record U disk, fault alarm record
- The whole machine is installed, the system has been tested in the factory, and the user only needs to install the power supply, gas pipeline, and cooling water pipeline before it can run
- Factory test: Each unit is tested in the factory with load for no less than 12 hours
- Factory test standard: ambient temperature 20 degrees, cooling water temperature 20 degrees, 6bar dry compressed air
Model | LQ-4015 | LQ-4030 | LQ-4060 | LQ-40100 | LQ-7515 | LQ-7530 | LQ-7560 | LQ-75100 | LQ-A1015 | LQ-A1030 | LQ-A1060 | LQ-A10100 |
LQ-4015W | LQ-4030W | LQ-4060W | LQ-40100W | LQ-7515W | LQ-7530W | LQ-7560W | LQ-75100W | LQ-A1015W | LQ-A1030W | LQ-A1060W | LQ-A10100W | |
Gas flow | 15m3/h | 30m3/h | 60m3/h | 100m3/h | 15m3/h | 30m3/h | 60m3/h | 100m3/h | 15m3/h | 30m3/h | 60m3/h | 100m3/h |
lowest temp. | -40℃ | -40℃ | -40℃ | -40℃ | -75℃ | -75℃ | -75℃ | -75℃ | -110℃ | -110℃ | -110℃ | -110℃ |
Heat exchange area | 0.8m2 | 1.5m2 | 3m2 | 5m2 | 1.5m2 | 2.5m2 | 5m2 | 9m2 | 2.5m2 | 4m2 | 8m2 | 13m2 |
Heat exchanger material | Standard configuration sus304 contains a small amount of copper | |||||||||||
Gas inlet and outlet diameter | ZG3/8 | ZG1/2 | ZG1 | DN50 | ZG3/8 | ZG1/2 | ZG1 | DN50 | ZG3/8 | ZG1/2 | ZG1 | DN50 |
Control System | Programmable controller and module | |||||||||||
Display and record | 7-inch color touch screen, record curve temperature and alarm conditions | |||||||||||
compressor | Tecumseh / Emerson Copeland | |||||||||||
Power supply | 220V 50HZ | 220V 50HZ | 380V 50HZ | 380V 50HZ | 220V 50HZ | 220V 50HZ | 380V 50HZ | 380V 50HZ | / | / | / | / |
1.2KW | 1.8KW | 3.5KW | 7KW | 2KW | 3KW | 6KW | 11.5KW | / | / | / | / |
Model | LQ-A1015W | LQ-A1030W | LQ-A1060W | LQ-A10100W |
Gas flow | 15m3/h | 30m3/h | 60m3/h | 100m3/h |
Low temp | -110℃ | -110℃ | -110℃ | -110℃ |
Heat exchanger material | sus304 Contains a small amount of red copper | sus304 Contains a small amount of red copper | sus304 Contains a small amount of red copper | sus304 Contains a small amount of red copper |
Gas inlet and outlet diameter | G3/8 | G1/2 | G1 | DN50 |
Control system | Programmable controller and module | |||
Display and record | 7-inch color touch screen, record curve temperature and alarm conditions | |||
compressor | Tecumseh / Emerson Copeland |
Product Applications
Used for cooling gas (non-corrosive): normal temperature gas such as dry compressed air, nitrogen, argon, etc. is passed into the LQ series equipment, the gas out can reach the target low temperature temperature, and the component or heat exchanger that needs to be tested can be supplied middle.
Recommended ProductsUsed for Reaction
loading…
已经是到最后一篇内容了!